
Reuso de efluentes em torres de resfriamento - estudo conceitual: Aeroporto Internacional do Rio de Janeiro
2010; Editora da Universidade Estadual de Maringá (Eduem); Volume: 32; Issue: 3 Linguagem: Inglês
10.4025/actascitechnol.v32i3.865
ISSN1807-8664
AutoresDenize Dias de Carvalho, Bernardo José Farah Machado,
Tópico(s)Water Quality and Pollution Assessment
ResumoWater reuse is an important tool in water management; it is a concept that promotes optimization of the water resource, reducing and often even eliminating environmental impacts. In this work, the composition of a secondary effluent (from the effluent treatment station (ETE APOIO) at Rio de Janeiro International Airport) was analyzed, with the aim of determining an adequate process for the reutilization of this effluent as replacement cooling water. Chemical analyses such as cation and anion analysis, BOD and COD were performed. Based on these analyses, it was found that TDS – Cl- was the critical parameter for effluent processing. A treatment system was proposed for effluent reuse including reverse osmosis; the cost estimate per m3 produced by this system was R$ 2.90 m-3.
Referência(s)