Artigo Revisado por pares

Control Strategies for AC Fault Ride Through in Multiterminal HVDC Grids

2014; Institute of Electrical and Electronics Engineers; Volume: 29; Issue: 1 Linguagem: Inglês

10.1109/tpwrd.2013.2281331

ISSN

1937-4208

Autores

Bernardo Silva, Carlos Moreira, Hélder Leite, João Peças Lopes,

Tópico(s)

Frequency Control in Power Systems

Resumo

A fully operational multiterminal dc (MTDC) grid will play a strategic role for mainland ac systems interconnection and to integrate offshore wind farms. The importance of such infrastructure requires its compliance with fault ride through (FRT) capability in case of mainland ac faults. In order to provide FRT capability in MTDC grids, communication-free advanced control functionalities exploiting a set of local control rules at the converter stations and wind turbines are identified. The proposed control functionalities are responsible for mitigating the dc voltage rise effect resulting from the reduction of active power injection into onshore ac systems during grid faults. The proposed strategies envision a fast control of the wind turbine active power output as a function of the dc grid voltage rise and constitute alternative options in order to avoid the use of classical solutions based on the installation of chopper resistors in the MTDC grid. The feasibility and robustness of the proposed strategies are demonstrated and discussed in the paper under different circumstances.

Referência(s)