The Apple Grove 750-kV Project- 500-kV Switching Surge and Line Flashover Tests
1965; Institute of Electrical and Electronics Engineers; Volume: 84; Issue: 7 Linguagem: Inglês
10.1109/tpas.1965.4766228
ISSN0018-9510
AutoresH. C. Barnes, A. J. McElroy, D. F. Shankle, H. M. Smith,
Tópico(s)Power Systems Fault Detection
ResumoRational design of extra-high-voltage systems depends on analytic studies to predict switching surge overvoltage magnitude and probability, and on laboratory tests for tower system switching surge withstand capability. Laboratory tests have been confined to ideal waveforms applied to single window configurations. Correlation with flashover performance of a typical 3-phase installation exposed to actual switching surge waveforms is attempted. The influence of interphase coupling and multiple circuit breaker operations in promoting multiphase flashover, which may curtail system performance margins, is also studied.
Referência(s)