Electronic Frequency Converter Feeding Single-Phase Circuit and Controlling Feeder Voltage With Fixed Power Factor Method for Shinkansen
2012; Institute of Electrical and Electronics Engineers; Volume: 27; Issue: 9 Linguagem: Inglês
10.1109/tpel.2012.2190302
ISSN1941-0107
AutoresKen Kunomura, Mitsuru Onishi, Masahiko Kai, Naotaka Iio, Midori Otsuki, Yoshinori Tsuruma, Naoya Nakajima,
Tópico(s)Power Systems and Technologies
ResumoIn the Tokaido Shinkansen, the instantaneous feeding power of substations has increased because of the high-density train schedule and the improved acceleration performance of the rolling stock. If the load power of feeding substations increases any further, it will not be possible to maintain the feeder voltage when the power converter supplies only reactive power. In consideration of such a situation in the frequency conversion section, an electronic frequency converter that controls the ac voltage using a fixed power factor method was developed. The superiority of the proposed control method is confirmed with electromagnetic transient program calculations and field test results. The electronic frequency converter has been in operation since February 2009 with good performance, showing the success of the system development described in this paper.
Referência(s)