Investigation of the insulation performance of the insulator covered with Lichen

1990; Institute of Electrical and Electronics Engineers; Volume: 5; Issue: 3 Linguagem: Inglês

10.1109/61.58010

ISSN

1937-4208

Autores

K. Naito, Ryosuke Matsuoka, Kenji Sakanishi,

Tópico(s)

High voltage insulation and dielectric phenomena

Resumo

The results of an investigation of the dielectric strength of lichen-contaminated insulators removed from actual transmission lines of three different countries are reported. All of the insulators showed low equivalent salt-deposit density. It seems that lichen on its own cannot cause flashover of the insulators. Flashover may be caused only if the thickness of the lichen is very great and/or there is superposition of salt. >