Feature Difference Index Analysis on Frequency Response Fingerprint of Transformer Windings
2010; Power System Technology Press; Linguagem: Inglês
ISSN
1000-3673
Autores Tópico(s)Power Quality and Harmonics
ResumoFrequency response analysis is an important method to detect transformer winding deformation.Experienced professionals can judge the winding deformation accurately by analyzing feature differences of transformer wingding frequency response fingerprint.Based on main points of experience,a new method to quantitatively analyze feature differences of frequency response fingerprint is proposed.Firstly,the amplitude difference is represented by amplitude difference index and the frequency difference is represented by frequency difference index;secondly,the feature difference indices are calculated by amplitude difference index and frequency difference index respectively;finally,transformer winding deformation can be judged through the feature difference indices.Verification results of more than 500 sets of diagnostic data show that the proposed method is evidently better than existing quantitative analysis method,and high judging accuracy can be attained.
Referência(s)