Artigo Acesso aberto Revisado por pares

Fire Risk in MTBF Evaluation for UPS System

2016; VSB – Technical University of Ostrava; Volume: 14; Issue: 2 Linguagem: Inglês

10.15598/aeee.v14i2.1662

ISSN

1804-3119

Autores

Stefano Elia, Alessio Santantonio,

Tópico(s)

Power System Reliability and Maintenance

Resumo

The reliability improvement of no-break redundant electrical systems is the first aim of the proposed strategy.The failure of some UPS (Uninterruptible Power Supply) system may lead to the fire occurrence.The most used electrical configurations are presented and discussed in the paper.The innovation of the proposed method consists of taking into account the fire risk to improve the accuracy of wiring configuration and components' failure rate.Thorough research on MTBF (Mean Time Between Failure) data has been performed for each wiring component and UPS.The fire risk is taken into account introducing an equivalent fire block in the Reliability Block Diagram scheme; it has an MTBF value calculated form yearly statistics of UPS fire events.The reliability of the most used UPS electrical configurations is evaluated by means of the RBD method.Different electrical systems have been investigated and compared based on MTBF.The importance of fire compartmentation between two or more UPS' connected in parallel is proved here.

Referência(s)