Interactions Between Indirect DC-Voltage Estimation and Circulating Current Controllers of MMC-Based HVDC Transmission Systems
2017; Institute of Electrical and Electronics Engineers; Volume: 33; Issue: 1 Linguagem: Inglês
10.1109/tpwrs.2017.2709789
ISSN1558-0679
AutoresHarith R. Wickramasinghe, Georgios Konstantinou, Josep Pou, Vassilios G. Agelidis,
Tópico(s)High-Voltage Power Transmission Systems
ResumoEstimation-based indirect dc-voltage control in MMCs interacts with circulating current control methods. This paper proposes an estimation-based indirect dc-voltage control method for MMC-HVDC systems and analyzes its performance compared to alternative estimations. The interactions between estimation-based indirect dc-voltage control and circulating current control methods, active/reactive power regulation are also investigated. The proposed method delivers similar performance to measurement-based direct dc-voltage control, regardless of the circulating current control method. Steady-state and transient performance is demonstrated using a benchmark MMC-HVDC transmission system, implemented in a real-time digital simulator. The results verify the theoretical evaluations and illustrate the operation and performance of the proposed indirect dc-voltage control method.
Referência(s)